This wireless charge and air measurement kit offers HVACR technicians a complete overview of the operation of a refrigeration, air conditioning, or heat pump system. The set includes six measuring instruments: two pressure probes, two temperature clamps, and two flexible psychrometers.
All measured values are transmitted directly via a 2.4GHz connection to a compatible mobile device with the Job Link app. The wireless range is up to 305 meters. This allows pressure, pipe temperature, air temperature, and relative humidity to be monitored from a single central location.
The JL3PR pressure probes measure from 0 to 580 psig and feature a right-angle 1/4-inch connection. The JL3PC pipe clamp probes are suitable for electrically conductive pipes with a diameter of 6.4 to 34.9 mm. A buzzer and LED indicate when the measurement is stable. The flexible JL3RH psychrometers measure temperatures from -40 to 121 °C and a relative humidity of 0 to 100%.
Each probe operates on two AAA batteries and has a battery life of approximately 150 hours. The instruments switch off automatically after two hours, but this function can be deactivated. The complete set comes with twelve batteries and a padded carrying case.
Specifications:
-
Product type: wireless charging and air measurement kit
-
Model: Job Link Charge and Air Kit
-
Article number: FPI-8800-000
-
Wireless range: up to 305 meters
-
Wireless frequency: 2.4 GHz
-
Connection: Bluetooth Low Energy
-
Suitable app: Job Link
-
Minimum Bluetooth version: BLE 4.0
-
Minimum iOS version: iOS 7.0
-
Minimum Android version: Android 5.0
-
Batteries per probe: 2 x AAA
-
Total number of batteries included: 12
-
Average battery life: approximately 150 hours
-
Automatic shutdown: after 2 hours
-
Automatic shutdown deactivatable: yes
-
Suitable for A2L applications: yes
Contents of the set:
-
2 x JL3PR cordless pressure probe
-
2 x JL3PC cordless pipe clamp probe
-
2 x JL3RH flexible psychrometer probes
-
1 x padded carrying bag
-
12 x AAA batteries
JL3PR pressure probe specifications:
-
Measurement range: 0 to 580 psig
-
Measuring range: 0 to 4000 kPa
-
Best accuracy: ±1 psig or ±7 kPa
-
Maximum overload: 800 psig or 5500 kPa
-
Connection: right-angle 1/4 inch female flare connector
-
Water resistance: designed according to IP55
Specifications JL3PC pipe clamp probe:
-
Suitable pipe diameter: 6.4 to 34.9 mm
-
Suitable pipe diameter: 1/4 to 1 3/8 inch
-
Suitable for: electrically conductive cables
-
Measuring range: -46 to 125 °C
-
Accuracy: ±0.6 °C
-
Average stabilization time: approximately 3 seconds
-
Measurement feedback: beeper and LED
-
Water resistance: designed according to IP55
-
Patent number: 10,365,165
Specifications JL3RH psychrometer probe:
-
Temperature measuring range: -40 to 121 °C
-
Relative humidity measuring range: 0 to 100% RH
-
Best temperature accuracy: ±0.6 °C
-
Best humidity accuracy: ±2.5% RH
-
Flexible probe diameter: 9 mm
-
Flexible probe length: 235 mm